PPT Slide
- Distribution pump control
Flow and energy measurement, Max flow = 1280 m3/hr
Differential pressure transmitter at plant outlet
Variable Distribution pump sets (Running : 1 variable and 1 constant, 1 variable speed standby) via Diff Pressure feedback control c/s sequence
Pressure transmitter at plant outlet (Max pressure = 9 bar)
Differential pressure feedback from network for pump speed control (only healthy reading could/would be selected)
Energy metering Sensors (matched pairs)