Mauritius Commercial Bank (Mauritius)

MCB incorporates an STL-AC.00-22
50% saving on operating costs


MCB Building



Cristo'Pak


Cristo'Control


STL Tank

 

 

In 2001, the Mauritius Commercial Bank Ltd decided to replace the two air cooled chillers located on the roof of its MCB Centre at Sir William Newton street in Port Louis, Mauritius.

The existing chillers were not in good condition and the maintenance costs were getting prohibitive. With the rising cost of electricity, it was decided to take this opportunity to reduce the rating of the chillers through the installation of a TES with an advanced control system, to be able to take advantage of future off peak reduced tariffs announced by the Central Electricity Board.

At the end of 2002, a “Cristo’Pak” with associated “Cristo’Control” using the latest communication technologies (remote management, e-reporting and preventive maintenance) was installed and this enabled the installation of two new chillers of nominal capacity 470 kW in replacement of the existing 750 kW chillers. The installation was commissioned in early 2003.

The Cristo'Control is able to optimize automatically the use of the Thermal Energy Storage (STL) according to the real cooling demand and to control the installation by remote management. In addition, the performances of the installation can be followed by Internet and the electrical consumption is measured. 

Technical Data

Daily Cooling Energy Consumption

:

5,600 kWh

Maximum Cooling Demand

:

750 kW

Cristo'Pak capacity

:

750 kW
Cristo'Control System
Chiller capacity

:

435 kW

Cooling Energy Stored

:

1,500 kWh

STL Storage Volume

:

27 m³

Number of Tank

:

1

Characteristics

The Cristo'Pak has a capacity of 750 kW. It is controlled with a Cristo'Control system developed by Cristopia.

The chiller (435 kW at 5/10°C and 270 kW in charge mode at -5.8/2.7°C) and the STL tank of   27 m³ are connected directly to the Cristo'Pak.

The tank is horizontal on cradles and located on the building roof.

Technical Advantages

Smaller chiller capacity
Reduced maintenance
Efficient and reliable system
Efficient energy management with Cristo'Control
Remote management & preventive maintenance
E-reporting

Projects Credits

Customer: MCB
Consultant: PROBURO
Installing Company: JL Air Conditioning & Refrigeration Ltd

 

 42% reduction of chiller capacity due to the Cristo'Pak 
Efficient energy management thanks to the Cristo'Control

Financial Advantages

Saving on operating costs, maintenance, demand charge and off peak consumption